Beijing Kylin Power & Technology Incorporated Co., Ltd.
Products
Contact Us
  • Contact Person : Ms. Song Wendy
  • Company Name : Beijing Kylin Power & Technology Incorporated Co., Ltd.
  • Tel : 86-10-62924806
  • Fax : 86-10-62924807
  • Address : Beijing,Beijing,No. 16 Anningzhuang East Road, Haidian District, Beijing
  • Country/Region : China
  • Zip : 100085

24kV, 600A Electrical Separable Premolded Deadbreak Rear Tee Cable Connectors

24kV, 600A Electrical Separable Premolded Deadbreak Rear Tee Cable Connectors
Product Detailed
Related Categories:Connectors
1) EOM is accepted 2) Exported to Korea, Vietnam, India and Brazil 3) AC withstand and partial discharge is done on each

Separable Rear Tee Connector is a fully shielded, molded rubber connector. It is designed to connect polymeric insulated cable to 600A Deadbreak Apparatus bushing that meets DIN47636 Standard of MV equipments, such as transformers, switchgears etc. Mated with the Conductive Connecting Rod, Separable Rear Tee Connector can be connected with the Front Tee Connector to form multi branches for single core synthetic 12, 17.5 and 24 kV cables. With Sections from 35 up to 500 mm².

Technical Parameters

No.

Item

Parameter

1

Rated Voltage

15kv

24kv

2

Rated Current

200A/600A

600A

3

AC Withstand Voltage Test

No breakdown occurred

at 40kv for 5min

No breakdown occurred

at 54kv for 5min

4

Partial Discharge Test at ambient temperature

15kv≤4pc

20kv≤4pc

5

Partial Discharge Test   (with 95~100°C)

15kv≤4pc

20kv≤4pc

6

Impulse Withstand Voltage Test at ambient temperature

No breakdown occurred at 10 positive and 10 negative impulses of 95kv

No breakdown occurred at 10 positive and 10 negative impulses of 125kv

7

Impulse Withstand Voltage Test at 95~100°C

No breakdown occurred at 10 positive and 10 negative impulses of 95kv

No breakdown shall occur at 10 positive and 10 negative impulses of 125kv

8

Heating cycle voltage test

No breakdown occurred on the samples subjected to 30 cycles in air and 30 cycles under water at the conductor temperature of 95~100°C and 23kv

No breakdown occurred on the samples subjected to 30 cycles in air and 30 cycles under water at the conductor temperature of 95~100°C and 30kv

9

Leakage current on Screen

16kA, 1s/22.7kA, 2s

22.7kA, 2s

10

Resistance test on Screen

40kA/81.1kA

81.1kA

24kV, 600A Electrical Separable Premolded Deadbreak Rear Tee Cable Connectors



Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.